You are here: Home >> Industries & Products >> Switching Power Supply >> Din Rail Series >> DR-75 Switching Power Supply
86-577-61989999 86-577-61891122 cncele@cncele.com cncelegroup@hotmail.com CNC.ELE.GROUP
DR-75 Switching Power Supply
DR-75 Switching Power Supply
bookmark this page Bookmark This Page
live messenger Live Messenger
skype me Skype Me
e-mail us cncele@cncele.com
Send Inquiry Send Inquiry
catalogue download Catalogue Download


 

Product Description: 

Model / Specification

DR-75-12

DR-75-24

DR-75-48

DC output voltage

12V

24V

48V

Output voltage error (Note2)

±2%

±1%

±1%

Rated output current

6.3A

3.2A

1.6A

Output current rage

0-6.3A

0-3.2A

0-1.6A

Wave and noise(Note3)

100mVp-p

150mVp-p

240mVp-p

Inlet stability(Note4)

±0.5%

±0.5%

±0.5%

Load stability(Note5)

±1%

±1%

±1%

DC output power

75.6W

76.8W

76.8W

Efficiency

76%

80%

81%

Adjustable range for DC voltage

10.8-13.2V

21.6-26.4V

43.2-52.8V

AC input voltage range

88264 4763HZ;248370VDC

Input current

1.8A/115V 0.90A/230V

AC lnrush current

Cold-start current 30A/115V 60A/230V

Leakage current

<3.5mA/240VAC

Overload protection

105%150% TypePULSING HICCUP SHUTDOWN Reset. auto recovery

Over-voltage protection

13.8-16.2V

37.6-32.4V

58-62V

High-temperature protection

 

 

 

Temperature coefficient

±0.03%(050)

Setup rise hold up time

1000ms,60ms,50ms/230VAC

Vibration

10500Hz,2G 10min./1cycle,Period for 60min,Each axes

Withstand voltage

Input and output interval1.5KVACInput and enclosure1.5KVACOutput and enclosure0.5KVAC

Isolation resistance

Input and output intervalInput and enclosureOutput and enclosure500VAC/100M Ohms

Working temperature and humidity

-10+5020%90%RH

Store temperature and humidity

-20+85,10%95RH

Overall dimension

55.5*125.2*100mm

Weight

0.55Kgs 20PCS/14KG/1.1CUFT

Safety standards

Meet UL1012

EMC standards

Meet Part 15J conduction class B

Note:1.The testing condition for the parameter above is:230VAC input, rated load,25 70%Rh,Humidity
2.Error,include the setting error, line stability and load stability.(Note:5)
3.Wave test:adopting“A12”double wire for 20MHz,and 0.1uF&uF capacitor short-circuit for interrupting
4.Inlet voltage stability test: when is over load, the lowest voltage of inlet is representative to the highest voltage.
5.Load stability test: The load is from 0% to 100%,others 60%.
6.C2311must be knocked down.

SendMessage